BWR-04□(TH) series transformer winding thermometer
- Details
BWY-04□ (TH) series transformer oil temperature controller is a transformer-specific instrument designed using the principle of compound temperature rise. Applicable to transformer and other equipment temperature detection and control. The instrument has and good protection performance, can work normally in outdoor conditions, the instrument is equipped with four to six adjustable control switches, can be used for transformer cooling system control and signal alarm, over-temperature tripping. Through embedded in the primary table temperature transmitter or Pt100 platinum resistance, can output and temperature value corresponding to the DC (4-20) mA current signal or Pt100 platinum resistance signal, for the computer system and the use of the secondary instrumentation, to achieve unmanned power station management.
Description:
Technical parameters
I. Working conditions: ambient temperature (-40~+55)℃, relative humidity ≤95%RH
II. Temperature transmitter power supply:AC/DC(100-260)V,Frequency 50Hz
III. Measuring range: (0~150)℃
IV. Accuracy: 2.0 grade (according to standard JB/T8450-2016)
V. Switching performance: four adjustable switches (up to 6 groups according to user requirements)
VI. Switch action point: K1=50℃, K2=75℃, K3=100℃, K4=120℃.
VII. Switch rated power: AC220V/5A
VIII. Switch action difference: ±2℃, switch switching difference: (6±2)℃
IX. Temperature package size: φ14, insertion depth not less than 150mm
X. Installation thread: (M27x2)mm or (M33x2)mm
XI. Capillary length: 6m
XII. Protection grade: IP55
XIII. Product installation size chart:
Note: The above technical descriptions are all standard settings for our products, if customers have special requirements for measuring range, switching action points, installation dimensions, etc. can be customized according to customer needs.
type | Secondary rated current Ip(A) | Output current Is(A) | Adjust line ends K |
A | 5≥Ip>3 | (32~38)%×Ip | 3 |
(24~32)%×Ip | 4 | ||
(15~24)%×Ip | 5 | ||
(10~15)%×Ip | 6 | ||
B | 3≥Ip>2 | (50~60)%×Ip | 3 |
(40~50)%×Ip | 4 | ||
(28~40)%×Ip | 5 | ||
(17~28)%×Ip | 6 | ||
C | 2≥Ip>1 | (75~90)%×Ip | 3 |
(60~75)%×Ip | 4 | ||
(40~60)%×Ip | 5 | ||
(25~40)%×Ip | 6 | ||
D | 1≥Ip>0.61 | (150~180)%×Ip | 3 |
(120~150)%×Ip | 4 | ||
(100~120)%×Ip | 5 | ||
(50~100)%×Ip | 6 |
Our Advantage
* Cheap
* Customization acceptable
* Good accuracy